| Cell type | LFP 3.2V/280Ah |
| Max. charging/discharging rate | 0.5P |
| Cell combination method | 1P240S |
| PACK number | 5 pcs |
| Battery capacity | 768V |
| Voltage range | 672V~864V |
| Cooling method | Liquid cooling |
|
|
|
| Rated AC power | 100 kW |
| Rated voltage | 400 Vac |
| Rated AC Current | 145A |
| AC side wiring method | Three-phase, Four-wire |
| Grid voltage range | 340-460 Vac |
| Cooling method | Intelligent forced air cooling |
| Power factor | -0.99-0.99 |
| THD of current | ≤3% (Full Load) |
| Current DC component | ≤0.5% |
| Grid frequency range | 50/60 Hz+ 2.5HZ |
|
|
|
| Ambient temperature | 20℃~55°℃,Derating over>45°C |
| Humidity | ≤95%RH,no condensation |
| Altitude | ≤2000m |
| Protection level | IP55 |
| Firefighting method | Aerosol |
| Anti-corrosion grade | C5 Standard |
| Communication interface/protocol | Ethenet (LAN )/Modbus TCP |
| Dimension(WidthxDepthxHeight | 1300x1300x2300 mm |
| Weight | ~2800kg |
| Certification | AS/NZS 3000, AS/NZS 3008.1.1, AS/NZS 60947.1,AS/NZS 5139:2019, Battery Best Practice Guide, CEc listed |
|
|
|
| Rated AC Power | 100kVA |
| AC side wiring method | Three-phase, Four-wire |
| Cooling method | Intelligent forced air cooling |
| Power factor | -0.99-0.99 |
| THD of current | ≤3% (Full Load) |
| Current DC component | ≤0.5% |
| Grid frequency range | 50/60 Hz ± 2.5Hz |